VARIABLE INLET VANE DAMPERS
|

|
-
VIV dampers are often used for capacity
modulation. They give accurate modulation and power savings over other
styles of dampers at reduced air flow.
-
For every inlet vane position there is
different capacity v/s static pressure curve and capacity v/s brake
horsepower curve generated by the blower.
-
When an inlet vane is partially closed,
each blade directs the air into the impeller in the direction of
rotation and so the air is prespun. This brings about a reduction in
the capacity, static pressure and BHP. The amount of BHP savings at
reduced capacity is determined by the type of system and type of
blower-vane combination.
-
Inlet guide vanes are synchronously
adjustable in the same angular position by a connecting element.
-
Adjustment can be made either automatically
via an adjusting element by pneumatic / electrical or hand.
|
|
Home |
Enquiry
|
|
|